beautypg.com

23 configuration – batches/plants – West Control Solutions DataVU 7 User Manual

Page 167

background image

167

23 Configuration – Batches/Plants

Batch start

This parameter defines how the batch report for a plant will be started and
stopped.

Control signal

The control signal can only be activated if batch reporting is set to be started
by a binary signal.

Start index ...

This parameter is used as the start marker for binary linking. If binary linking is
active for a batch text, then one of the 128 device-internal batch texts can be
inserted into a current batch report immediately after the “Start at text”
position.

Binary linking
(logic operation)
1 — 6

Depending on the settings, binary linking allows up to 64 different texts to be
incorporated into the batch report under control of the binary signals.

Up to 128 batch texts are available, which can be defined in the setup
program. The batch text that is used is defined by the “Start at text” parameter
and “Logic operation”.

Inactive

Batch reporting cannot be started.

Control knob

Batch reporting can be started and stopped by the
operator, using the control knob on the instrument.

Binary signal

Batch reporting is started and stopped by one of the
binary signals.

Bar code

Batch reporting is started and stopped by a barcode
reader.

H

If the “Batch start” parameter is set to “Binary signal”, and the
“Control signal” parameter is set to “inactive”, then batch reporting
cannot be started. If “Control signal” is active, then a binary signal
must be selected.

H

Batch text used = Start at text + logic combination