20 Configuration - Limit Monitoring

Nine limit values are available for limit monitoring, in addition to the alarms at
channel level.

For a description of the alarms at channel level, see Chapter 13.4 "Alarm
configuration".

20.1 Function … Alarm Configuration

Overview

Function

“Low alarm” and “High alarm” are available for each limit value.

Analog value

Analog value determines the internal or external analog input that is to be
monitored.

(1)

(2)

(3)

(3)

alarm on

alarm off

(1) = Low alarm (limit value)
(2) = High alarm (limit value)
(3) = Hysteresis

Inactive

Limit monitoring is switched off.

Low alarm

Binary signal “Limit monitoring 1 — 9” is activated when
the value falls below the limit.

High alarm

Binary signal “Limit monitoring 1 — 9” is activated when
the value goes above the limit.