22 configuration - interface – West Control Solutions DataVU 7 User Manual
Page 160

22 Configuration - Interface
160
Addr. ext.
binary value
A maximum of 24 external binary tracks (binary values) can be read into the
paperless recorder. The following parameters must be configured for each
binary variable.
Number of
measurements
The number of measurements to be read. The number
“1” means that one measurement is made at every
cyclical interval. If a number larger than 1 is entered,
then (commencing at the Modbus address) several
measurements will be read and automatically distributed
to the following external inputs (analog values). The
entry template will be locked for subsequent values.
Example: starting at "Ext. analog value1“, three
measurement values are read. In the menu, the settings
for “Ext. analog value 2“ and "Ext. analog value 3“ are
locked. starting at "Ext. analog value 4”, a new
arrangement can be configured.
Data format
Selection of the format in which data are to be received.
For the float format, you can define whether the LSB
(least significant bit) or MSB (most significant bit) is
transmitted first.
In the unsigned integer format (UInt: 0 — 65535) and the
integer format (Int: -32768 — 32767) you can define a
divisor for the division of the data that are received. The
purpose of the division is to make it possible for floating
point values to be transmitted in integer format. So the
sender must multiply the data by the corresponding
factor before transmission.
Device address
The address of the slave device from which data
are to be fetched.
Modbus address
Address within the instrument.
v See the instrument documentation for the slave device.
Bit number
The bit (b0 — b15) that is to be read.
v See the instrument documentation for the slave device.
Bit quantity
The number of bits to be read. The number “1” means
that one bit is read at every cyclical interval. If a number
larger than 1 is entered, then (commencing at the
Modbus address) several bits will be read and
automatically distributed to the following external binary
values. The entry template will be locked for subsequent
values.
Example: starting at "Ext. binary value 1“, 16 bits are
read. In the menu, the settings for “Ext. binary value 2“
to "Ext. binary value 16“ are locked. starting at "Ext.
binary value 17”, a new arrangement can be configured.