ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
59407, Issue 1 – March 2008
Modbus Parameters
Page 97
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Value
Output 4C Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
Output 4C Alarm
Selection
2236
0x08BC
R/W
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Value
Output 4D Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
Output 4D Alarm
Selection
2237
0x08BD
R/W
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse