Output Configuration
A sub-menu of Configuration Mode used to adjust the parameters that relate to the Outputs
(Linear output type & scaling, output usage and scaling etc).
Also refer to: Configuration Mode and Linear Output.
Overlap/Deadband
Defines the portion of the primary and secondary proportional bands over which both outputs
are active (called Overlap), or neither is active (called Deadband). This is adjustable in the
range -20% to +20% of the sum of the two proportional bands. Positive values = Overlap,
negative values = Deadband.
.
Figure 51.
Overlap/Deadband
Overlap/Dead
Output 1
Output 1
Output 2
Output 2
Output 2
Process Variable
Process Variable
Process Variable
Proportional Band 1
Proportional
Band 1
Proportional
Band 1
Proportional Band 2
Proportional
Band 2
Proportional Band 2 = 0
Output 1
Output 1
Output 1
Output 1
Output 2
Output 2
Output 2
Overlap
(positive value)
Deadband
(negative value)
Negative values
Positive values
OVERLAP
WITH PID
DEADBAND
WITH PID
OVERLAP &
DEADBAND
WITH ON/OFF
Output Power (%)
Output Power (%)
Output Power (%)
Output 2 ON
Output 2 OFF
ON/OFF Differential