Option slot b parameters – West Control Solutions ProVU 4 User Manual
Page 87
ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
Page 86
Modbus Parameters
59407, Issue 1 – March 2008
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Value
Communications Status
0
Writing via serial communications disabled
Comms Write
Enable/Disable
2124
0x084C
R/W
1
Writing via serial communications enabled
Value
Auxiliary Input A Break Status
0
Inactive
Auxiliary Input A
Input Signal Break
2127
0x084F
RO
1
Active
Value
Auxiliary Input A Under Range Status
0
Inactive
Auxiliary Input A
Input Signal Under
Range
2128
0x0850
RO
1
Active
Value
Auxiliary Input A Over Range Status
0
Inactive
Auxiliary Input A
Input Signal Over
Range
2129
0x0851
RO
1
Active
Option Slot B Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Value
Auxiliary B Input Type
0
0 to 20mA DC
1
4 to 20mA DC
2
0 to 10V DC
3
2 to 10V DC
4
0 to 5V DC
5
1 to 5V DC
6
0 to 100mV DC
Auxiliary Input B
Type
2080
0x0820
R/W
7
>2000 Ohm Potentiometer
Value
Module Fitted In Slot B
0
None Fitted
1
Auxiliary Input B with Digital Input B
Option Slot B
Module Type
2081
0x0821
RO
255
Error (unrecognised module)
Value
Auxiliary Input B Break Status
0
Inactive
Auxiliary Input B
Input Signal Break
2082
0x0822
RO
1
Active
Value
Auxiliary Input B Under Range Status
0
Inactive
Auxiliary Input B
Input Signal Under
Range
2083
0x0823
RO
1
Active
Value
Auxiliary Input B Over Range Status
0
Inactive
Auxiliary Input B
Input Signal Over
Range
2084
0x0824
RO
1
Active
Value
Digital Input B Status
0
Inactive
Digital Input B Status
2085
0x0825
RO
1
Active
Value
Calibration Status
0
Calibration OK
Calibration Status
2086
0x0826
RO
1
Calibration Required