Time proportioning control, Trend display, Tuning – West Control Solutions ProVU 4 User Manual
Page 162: Tuning menu, Time proportioning, or, Tuned correctly each time the process is, Tuning and, And time proportional control, And time proportioning, Time proportioning control and

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
59407, Issue 1 – March 2008
Glossary
Page 161
Time Proportioning Control
Time proportioning control is accomplished by cycling the output on and off during the 
prescribed cycle time, whenever the process variable is within the proportional band(s). The 
PID control algorithm determines the ratio of time (on vs. off) to achieve the level of the 
correcting variable required to remove the control deviation error. E.g. for a 32 second cycle 
time, 25% power would result in the output turning on for 8 seconds, then off to 24 seconds. 
This type of output might be used with electrical contactors, solid state relays or solenoid 
valves. Time proportioning control can be implemented with Relay, Triac or SSR Driver 
outputs for either primary or secondary outputs.
Also refer to: Control Deviation, Correcting Variable, Current Proportioning Control, Cycle 
Time, PID, Primary Proportional Band, Relay, Secondary Proportional Band, Solenoid Valve, 
SSR and Triac.
Trend Display
Trend View is a graphical representation of recent process conditions. This feature is 
available on all variants. It does not rely on the Data Recorder option, and does not retain the 
stored data if the power is turned off. The trend shows the most recent 120 out of 240 stored 
data points. Its scale adjusts automatically for the best resolution for the visible data. This 
data can be the process variable; process variable & setpoint (shown as a doted line), or the 
minimum and maximum value of the process variable measured since the last sample. Any 
active alarm(s) are indicated above the graph. The user can scroll the right hand cursor line 
back to examine all 240 data points. The sample interval and data to display is set in Display 
Configuration.
Also refer to: Alarm Types, Display Configuration, Operation Mode, and Process Variable, 
Setpoint.
Tuning
PID Controllers must be tuned to the process in order for them to attain the optimum level of 
control. Adjustment is made to the tuning terms either manually, or by utilising the controller’s 
automatic tuning facilities. Tuning is not required if the controller is configured for On-Off 
Control.
Also refer to: Auto Pre-Tune, Controller, Derivative Action, Integral Action, On-Off control, 
PID, Pre-Tune, Primary Proportional Band, Self-Tune, Secondary Proportional Band and 
Tuning Menu.
Tuning Menu
The Tuning Menu can be accessed from the Main Menu. This menu is lock code protected.
It gives access to the Pre-tune, Auto Pre-Tune and Self-tune facilities. These assist with PID 
tuning, by setting up Proportional band(s), Integral and Derivative parameter values. Tuning 
is not required for On-Off control.
Pre-tune can be used to set PID parameters approximately. Self-tune may then be used to 
optimise the tuning if required. Pre-tune can be set to run automatically after every power-up 
by enabling Auto Pre-Tune.
Refer to the Automatic Tuning information in the Configuration & Use section.
Also refer to: Auto Pre-Tune, Derivative Action, Integral Action, Lock Codes, Main Menu, On-
Off control, PID, Pre-Tune, Primary Proportional Band, Self-Tune, Secondary Proportional 
Band and Tuning Menu. 
