ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
59407, Issue 1 – March 2008
Modbus Parameters
Page 123
Read Profile Header - Response (from instrument)
Field Name
Data
Comments
(Dec)
(Hex)
Profile Starting Setpoint High
00
00
Profile Starting Setpoint Low
A/R
A/R
0 = Current Setpoint, 1 = Current Process
Variable Value
Profile Recovery High Byte
00
00
Profile Recovery Low Byte
A/R
A/R
0 = Control to off, 1 = Restart profile,
2 = Maintain last profile setpoint
3 = Use controller setpoint, 4 = Continue
profile from where it was when power failed
Profile Recovery Time (Byte 4 - high)
Profile Recovery Time (Byte 3)
Profile Recovery Time (Byte 2)
Profile Recovery Time (Byte 1 - Low)
Floating point number
Profile Abort action High Byte
00
00
Profile Abort Action Low Byte
A/R
A/R
0 = Control to off
1 = Maintain last profile setpoint
2 = Use controller setpoint
Profile Cycles High Byte
A/R
A/R
Profile Cycles Low Byte
A/R
A/R
1 to 9999 or 10,000 for “Infinite”
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
Read A Segment
Read A Segment - Request (to instrument)
Field Name
Data
Comments
(Dec)
(Hex)
Unit Address
A/R
A/R
The ID address of the instrument as
required
Function Code
23
17
Requires the multi read/write function
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High Byte
00
00
Read Quantity Of Registers Low Byte
11
0B
Write Start Address High Byte
22
16
Write Start Address Low Byte
06
06
Write Quantity Of Registers High Byte
00
00
Write Quantity Of Registers Low Byte
03
03
Byte Count
06
06
Command Code High Byte
82
52
Command Code Low Byte
83
53
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
Segment Number High Byte
A/R
A/R
Segment Number Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to the Read A Segment request as follows: