West Control Solutions ProVU 4 User Manual
Page 97
ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
Page 96
Modbus Parameters
59407, Issue 1 – March 2008
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Value
Digital Output 4C Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
Digital Output 4C
Function
2232
0x08B8
R/W
4
Alarm and Event
Value
Digital Output 4D Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
Digital Output 4D
Function
2233
0x08B9
R/W
4
Alarm and Event
Value
Output 4A Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
Output 4A Alarm
Selection
2234
0x08BA
R/W
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Value
Output 4B Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
Output 4B Alarm
Selection
2235
0x08BB
R/W
13
OR of Alarm 1, 2, or 3. Reverse