Profiler control & status parameters – West Control Solutions ProVU 4 User Manual

Page 112

background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

59407, Issue 1 – March 2008

Modbus Parameters

Page 111

Parameter Name

Modbus Address

Access

Values

(Dec)

(Hex)

Value

Trend View Data

0

None (trend view off)

1

Process variable only

2

Process variable and setpoint

Values To Display In
Trend View

9001

0x2329

R/W

3

Process variable maximum & minimum
since last sample

Profiler Control & Status Parameters

Parameter Name

Modbus Address

Access

Values

(Dec)

(Hex)

Value

Profile Run/Hold Signal Source

0

Operator Key Press Only

1

Digital input A

Profile Run/Hold
Signal

8192

0x2000

R/W

2

Digital input B

Value

Profile Abort Signal Source

0

Operator Key Press Only

1

Digital input A

Profile Abort Signal

8193

0x2001

R/W

2

Digital input B

Active Profiler
Number

8243

0x2033

R/W

Currently selected profile number (1 to 64)

Active Segment
Number

8244

0x2034

RO

Currently active segment (1 to 255)

Value

Profiler Command

0

Do nothing

1

Run the currently selected profile

2

Hold the currently running profile

3

Abort the currently running profile

4

Jump to the next segment

5

Release the hold

Profiler Control
Commands

8245

0x2035

R/W

6

Exit profiler, return to controller mode

Note: The Profiler Control Commands must be followed by a Profiler Control Confirmation Action command.

Value

Implement Profiler Command

0

Do Not Implement Command

Profiler Control
Confirmation Action

8257

0x2041

R/W

1

Implement previous Profiler Command

Value

Editing Current Running Profile

0

Editing current running profile forbidden

Enable Edit While
Running

8262

0x2046

R/W

1

Editing current running profile allowed

Value

Profile Control From Operation Mode

0

Operation Mode profile control disabled

Profile Control In
Operation Mode

8260

0x2044

R/W

1

Operation Mode profile control enabled

Profile Cycles Run

8247

0x2037

RO

The Number of times the currently running profile has
cycled
Value

Status Of Event 1

0

Event 1 Inactive

Event 1 Status

8249

0x2039

RO

1

Event 1 Active