beautypg.com

Messages and error indications, Start-up errors, Configuration problem – West Control Solutions ProVU 4 User Manual

Page 40: Input problems, Un-calibrated input detection, 6 messages and error indications

background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

59407, Issue 1 – March 2008

Messages and Error Indications

Page 39

6 Messages and Error Indications

Start-up Errors

The following displays are shown when an error detected during the power-up self-test.

Option Module Problems

The “Option Slot n Error” display is shown when an error detected with the installed option
modules - where “n” is the slot number for the fault.

Replace the module in slot “n”. If this does not solve the problem, return the instrument for
servicing.

Configuration Problem

Warns if a problem has been detected with the instrument configuration. Check all settings
are correct before proceeding. If the problem persists, return the instrument for servicing.

CAUTION:

Correct the signal/wiring problem to continue normal operation. .

Input Problems

Sensor Break Detection

Whenever a problem is detected with the process variable or auxiliary input connections,
their displayed value is replaced with the word “OPEN”.
This may be the result of a failed sensor, a broken connection or an input circuit fault.
In this condition, the Control Outputs go to the pre-set power value (see Control
Configuration).

CAUTION:

Correct the signal/wiring problem to continue normal operation.

Un-Calibrated Input Detection

The instrument is fully calibrated during manufacture. If a fault occurs and the calibration
data becomes corrupted, the process input display is replaced with the word “ERROR”.
In this condition, the Control Outputs go to the pre-set power value (see Control
Configuration).

CAUTION:

Re-calibrate the input before continuing normal operation. If the problem persists,
return the instrument for servicing.