ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
Page 110
Modbus Parameters
59407, Issue 1 – March 2008
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
16
Profile Running
17
Profile Ended
Value
Backlight Colour
0
Green to Red on Alarm
1
Red to Green on Alarm
2
Permanent Green
Backlight Colour
7668
0x1DF4
R/W
3
Permanent Red
Value
Language
0
Main Display Language
Display Language
7675
0x1DFB
R/W
1
Alternate Display Language
Display Contrast
7676
0x1DFC
R/W
0 to 127
Value
Invert Display
0
Normal Display
Invert Display
7677
0x1DFD
R/W
1
Inverted Display
Setup Lock Code
7678
0x1DFE
R/W
1 to 9999. Default is 10
Configuration Lock
Code
7679
0x1DFF
R/W
1 to 9999. Default is 10
Tuning Lock Code
7680
0x1E00
R/W
1 to 9999. Default is 10
Supervisor Lock
Code
7681
0x1E01
R/W
1 to 9999. Default is 10
Profiler Lock Code
7682
0x1E02
R/W
1 to 9999. Default is 10
USB Lock Code
7683
0x1E03
R/W
1 to 9999. Default is 10
Recorder Lock Code
7684
0x1E04
R/W
1 to 9999. Default is 10
Value
Read Only Operation Mode
0
Operation Mode Read/Write
Read Only
Operation Mode
7685
0x1E05
R/W
1
Operation Mode Read Only
Value
Bar Graph Format
0
Power Output
1
Control Deviation
Bar Graph Format
7686
0x1E06
R/W
2
% Memory Remaining
Value
Trend Sample Interval
0
Every Second
1
Every 2 Seconds
2
Every 5 Seconds
3
Every 10 Seconds
4
Every 15 Seconds
5
Every 30 Seconds
6
Every Minute
7
Every 2 Minutes
8
Every 5 Minutes
9
Every 10 Minutes
10
Every 15 Minutes
Trend View Sample
Interval
9000
0x2328
R/W
11
Every 30 Minutes