Control parameters – West Control Solutions ProVU 4 User Manual
Page 102

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
59407, Issue 1 – March 2008
Modbus Parameters
Page 101
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Auxiliary Input B
Value
4081
0x0FF1
RO
The value of analogue Auxiliary Input B
Value
Setpoint Select
0
Local Setpoint 1
User Setpoint Select
4122
0x101A
R/W
1
Alternate setpoint
Setpoint Ramp Rate
4123
0x101B
R/W
0 to 10000 0 or >10000 = Off
Target Setpoint
4125
0x101D
RO
The target setpoint value when ramping
Value
Operator Access To Ramp Rate
0
Disabled
Operator Access To
Setpoint Ramp Rate
4126
0x101E
R/W
1
Enabled
Value
Selected Setpoint
0
Local Setpoint 1
Selected Setpoint
4127
0x101F
RO
1
Alternate setpoint
Actual Setpoint
8256
0x2040
RO
The current instantaneous value of the active setpoint
Control Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Value
Manual Control Selection Method
0
Automatic Control Only
1
Manual Control Only
2
User Selectable From Key Pad
3
Digital input A
Manual Control
Select Method
4299
0x10CB
R/W
4
Digital input B
Value
Control Enable Selection Method
0
Enabled Only
1
Disabled Only
2
User Selectable From Key Pad
3
Digital input A
Control Enable
Select Method
4300
0x10CC
R/W
4
Digital input B
Primary Cycle Time
4301
0x10CD
R/W
0.5 to 512.0 Seconds
Secondary Cycle
Time
4302
0x10CE
R/W
0.5 to 512.0 Seconds
Value
Control Type
0
Single Control
Control type
4310
0x10D6
R/W
1
Dual Control
Value
Control Type
0
Direct Acting
Control Action
4311
0x10D7
R/W
1
Reverse Acting
Primary Proportional
Band
4312
0x10D8
R/W
0.0 to 999.9 (% of Input Span)
Secondary
Proportional Band
4313
0x10D9
R/W
0.0 to 999.9 (% of Input Span)
Integral Time
Constant
4314
0x10DA
R/W
0.0 to 5999 Seconds