Profile end actions – West Control Solutions ProVU 4 User Manual
Page 72

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
59407, Issue 1 – March 2008
Profiler Option
Page 71
Possible Recovery Methods:
A Abort the profile and maintain the profile value from the time the power failed.
B Abort the profile and use Controller Setpoint value.
C Abort the profile with the Control outputs off.
D Restart the profile again from the beginning.
E Continue profile from the point it had reached when the power failed
Figure 44.
End, Abort and Recovery Actions
Profile End Actions
Once a running profile ends, that profiles’ Segment End Type defines action taken by the
instrument. If a sequence of profiles has been completed, the End Segment Type of the last
profile will be carried out. The possible end actions are explained below.
Possible Profile End Actions:
A At profile end, maintain the Final Setpoint value of the last segment.
B At profile end, exit Profiler Mode and use the Controller Setpoint value.
C At profile end, remain in Profiler Mode with the Control outputs off.
Figure 45.
Profile End Action
Controller SP
Run
(Start-on SP)
Power Off
Power On
= Control Off
Planned Profile
Power Off Time
Controller SP
Run
(Start-on SP)
Normal Profile End
= Control Off
Last Profile SP
Controller SP