ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
Page 112
Modbus Parameters
59407, Issue 1 – March 2008
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Value
Status Of Event 2
0
Event 2 Inactive
Event 2 Status
8250
0x203A
RO
1
Event 2 Active
Value
Status Of Event 3
0
Event 3 Inactive
Event 3 Status
8251
0x203B
RO
1
Event 3 Active
Value
Status Of Event 4
0
Event 4 Inactive
Event 4 Status
8252
0x203C
RO
1
Event 4 Active
Value
Status Of Event 5
0
Event 5 Inactive
Event 5 Status
8253
0x203D
RO
1
Event 5 Active
Value
Segment Type Status
0
No segment
1
Setpoint ramping up
2
Step
3
Dwell
4
Held
5
Loop
6
Join
7
End
Segment Type
Status
8258
0x2042
RO
8
Setpoint ramping down
Currently Active
Profile Name
8259
0x2043
RO
The name of the currently selected profile
Value
0
Profile running
1
Input sensor break
2
Profile not valid
3
Controller in manual mode
4
Profile finished. Profiler is maintaining
the last profile setpoint
5
Profile finished with control outputs off
Secondary Profile
Status
8232
0x2028
RO
6
Profile control has ended. Unit is
Controller Mode.
Delay time
8233
0x2029
RO
The current start delay time remaining
Current Profile
Running Time
8235
0x202B
RO
The elapsed time of the current running profile
Current Profile
Remaining Time
8236
0x202C
RO
The remaining time for the current running profile
Current Segment
Running Time
8237
0x202D
RO
The elapsed time of the current profile segment
Current Segment
Remaining Time
8238
0x202E
RO
The remaining time for the current profile segment
Total Hold Time
8239
0x202F
RO
Total time the current profile has been held
Current Segment
Loops Run
8240
0x2030
RO
The number of times the current looping segment has
looped back
Profile Setup
8198
0x2006
R/W
Refer to the Profile Setup Over Modbus
information below