beautypg.com

West Control Solutions ProVU 4 User Manual

Page 113

background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

Page 112

Modbus Parameters

59407, Issue 1 – March 2008

Parameter Name

Modbus Address

Access

Values

(Dec)

(Hex)

Value

Status Of Event 2

0

Event 2 Inactive

Event 2 Status

8250

0x203A

RO

1

Event 2 Active

Value

Status Of Event 3

0

Event 3 Inactive

Event 3 Status

8251

0x203B

RO

1

Event 3 Active

Value

Status Of Event 4

0

Event 4 Inactive

Event 4 Status

8252

0x203C

RO

1

Event 4 Active

Value

Status Of Event 5

0

Event 5 Inactive

Event 5 Status

8253

0x203D

RO

1

Event 5 Active

Value

Segment Type Status

0

No segment

1

Setpoint ramping up

2

Step

3

Dwell

4

Held

5

Loop

6

Join

7

End

Segment Type
Status

8258

0x2042

RO

8

Setpoint ramping down

Currently Active
Profile Name

8259

0x2043

RO

The name of the currently selected profile

Value
0

Profile running

1

Input sensor break

2

Profile not valid

3

Controller in manual mode

4

Profile finished. Profiler is maintaining
the last profile setpoint

5

Profile finished with control outputs off

Secondary Profile
Status

8232

0x2028

RO

6

Profile control has ended. Unit is
Controller Mode.

Delay time

8233

0x2029

RO

The current start delay time remaining

Current Profile
Running Time

8235

0x202B

RO

The elapsed time of the current running profile

Current Profile
Remaining Time

8236

0x202C

RO

The remaining time for the current running profile

Current Segment
Running Time

8237

0x202D

RO

The elapsed time of the current profile segment

Current Segment
Remaining Time

8238

0x202E

RO

The remaining time for the current profile segment

Total Hold Time

8239

0x202F

RO

Total time the current profile has been held

Current Segment
Loops Run

8240

0x2030

RO

The number of times the current looping segment has
looped back

Profile Setup

8198

0x2006

R/W

Refer to the Profile Setup Over Modbus
information below