Profile abort actions – West Control Solutions ProVU 4 User Manual
Page 73

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
Page 72
Profiler Option
59407, Issue 1 – March 2008
Profile Abort Actions
If a running profile is forced to end early, the Profile Abort Action defines action taken by
the instrument. This is set in the General Profile Configuration section of the Profile Setup
Menu.
The possible options are explained below.
Possible Profile Abort Actions:
A Abort the profile and maintain the value of the setpoint at the time of the abort.
B Abort the profile and exit Profiler Mode using the Controller Setpoint value.
C Abort the profile and remain in Profiler Mode with the Control outputs off.
Figure 46.
Profile Abort Action
Controller SP
Run
(Start-on SP)
Profile Aborted
= Control Off
Last Profile SP
Controller SP
- 2300 (18 pages)
- 3300 (2 pages)
- 4100+ (177 pages)
- N4100 (79 pages)
- N4400 (38 pages)
- N6500 (2 pages)
- N6600 (114 pages)
- N8800 (88 pages)
- N8840 (90 pages)
- 9300 (2 pages)
- 9500 (24 pages)
- D280-1 (49 pages)
- KS 40-1 (60 pages)
- KS 40-1 Burner (40 pages)
- KS 45 (76 pages)
- KS 50-1 (72 pages)
- KS 90-1 (84 pages)
- KS 90-1 Programmer manual (84 pages)
- KS 94 (44 pages)
- Pro-16 (88 pages)
- Pro-8 (72 pages)
- Pro-4 (84 pages)
- ProEC44 (274 pages)
- CI 45 (60 pages)
- SG 45 (56 pages)
- DataVU 5 (136 pages)
- DataVU 7 (208 pages)
- MRC 5000 Controller Manual (32 pages)
- MRC 5000 Recorder Manual (32 pages)
- MRC 7000 Controller Manual (74 pages)
- MRC 7000 Recorder Manual (64 pages)
- MRC 7000 Profiler Manual (84 pages)
- MRC 8000 (76 pages)
- MRC 9000 (318 pages)
- N8080 (for 1xxx) (40 pages)
- N8080 (for 2xxx) (39 pages)
- TB 40-1 Temperature Limiter (32 pages)
- TB 40-1 Temperature Monitor (32 pages)
- TB 45 Temperature Limiter (51 pages)
- TB 45 Temperature Monitor (52 pages)
- CALogix (44 pages)
- KS 800 Operating Instructions (36 pages)
- KS 800 ISO1745 Interface Manual (34 pages)
- KS 800 Profibus Interface Manual (52 pages)