Option slot 3 parameters – West Control Solutions ProVU 4 User Manual

Page 93

background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

Page 92

Modbus Parameters

59407, Issue 1 – March 2008

Parameter Name

Modbus Address

Access

Values

(Dec)

(Hex)

20

Event 4 AND Alarm 4. Direct Acting

21

Event 4 AND Alarm 4. Reverse Acting

22

Event 5 AND Alarm 5. Direct Acting

23

Event 5 AND Alarm 5. Reverse Acting

Output 2 Retransmit
Minimum

2182

0x0886

R/W

Limited by input range maximum/minimum

Output 2 Retransmit
Maximum

2183

0x0887

R/W

Limited by input range maximum/minimum

Option Slot 3 Parameters

Parameter Name

Modbus Address

Access

Values

(Dec)

(Hex)

Value

Module Fitted In Slot 3

0

None Fitted

1

Single Relay

2

Single SSR Driver

3

Linear mA/V DC

8

Triac

9

Dual Relay

10

Dual SSR Driver

11

24VDC Transmitter PSU

Option Slot 3
Module Type

2192

0x0890

RO

255

Error (unrecognised module)

Value

Linear Output 3 Type

0

0 to 5V DC

1

0 to 10V DC

2

2 to 10V DC

3

0 to 20mA DC

4

4 to 20mA DC

Linear mA/V DC
Output 3 Type

2193

0x0891

R/W

5

Variable 0 to 10VDC Transmitter PSU

Value

Digital Output 3 or 3A Status

0

Inactive

Digital Output 3 or
3A Status

2194

0x0892

RO

1

Active

Value

Digital Output 3B Status

0

Inactive

Digital Output 3B
Status

2195

0x0893

RO

1

Active

Linear Output 3
Level Status

2196

0x0894

RO

-2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Value

Linear Output 3 or 3A Function

0

Disabled

1

Primary Output Power

2

Secondary Output Power

3

Retransmit Actual Setpoint Value

Linear Output 3 or
3A Function

2203

0x089B

R/W

4

Retransmit Process Variable Value