Option slot 3 parameters – West Control Solutions ProVU 4 User Manual
Page 93
ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
Page 92
Modbus Parameters
59407, Issue 1 – March 2008
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Output 2 Retransmit
Minimum
2182
0x0886
R/W
Limited by input range maximum/minimum
Output 2 Retransmit
Maximum
2183
0x0887
R/W
Limited by input range maximum/minimum
Option Slot 3 Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Value
Module Fitted In Slot 3
0
None Fitted
1
Single Relay
2
Single SSR Driver
3
Linear mA/V DC
8
Triac
9
Dual Relay
10
Dual SSR Driver
11
24VDC Transmitter PSU
Option Slot 3
Module Type
2192
0x0890
RO
255
Error (unrecognised module)
Value
Linear Output 3 Type
0
0 to 5V DC
1
0 to 10V DC
2
2 to 10V DC
3
0 to 20mA DC
4
4 to 20mA DC
Linear mA/V DC
Output 3 Type
2193
0x0891
R/W
5
Variable 0 to 10VDC Transmitter PSU
Value
Digital Output 3 or 3A Status
0
Inactive
Digital Output 3 or
3A Status
2194
0x0892
RO
1
Active
Value
Digital Output 3B Status
0
Inactive
Digital Output 3B
Status
2195
0x0893
RO
1
Active
Linear Output 3
Level Status
2196
0x0894
RO
-2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Value
Linear Output 3 or 3A Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Retransmit Actual Setpoint Value
Linear Output 3 or
3A Function
2203
0x089B
R/W
4
Retransmit Process Variable Value