KROHNE MFC 010 C Converter User Manual
Page 55
MFC010 Interface Manual
53
Register No.
Description
1015
Tube Amplitude
- The sensor input amplitude to which the measuring tube oscillation control
system must aim to achieve. T he optimum setting for this value depends
upon the sensor type and size.
Format : Unsigned Integer
Range : 1% to 98%
Default Value: Dependent on Sensor Type and Size.
1016
Concentration Type
- The extrapolation method used by the General concentration
measurement c alculation s ub-system. (See Section 8.4 on page 76 for
more details)
Format : Unsigned Integer
Range :
0 = Linear
1 = Non-Linear
Default Value : 0
1017
Concentration 1 Product
- Determines the method by which the concentration value is represented
when a mixture two products, A & B, are being measured. (See Section 8.4
on page 76 for more details)
Format : Unsigned Integer
Range :
0 = % of Product A
1 = % of Product B
Default Value : 0
1018
Concentration Coefficient #5
- Definition of the carrier ( Product B ) w hen per forming t he G eneral
Concentration calculation. (See section 8.4 on page 76 for details)
Format : Unsigned Integer
Range:
0 = Pure Water (998.2 kg/m
3
@ 20°C)
1 = Town Water (999.7 kg/m
3
@ 20°C)
2 = Other.
Default Value : 0
1019
CT
Density Mode
- The mode by which the density value is generated. S ee section 8.3 on
page 75 for details.
Format : Unsigned Integer
Range:
0 = Actual (Measured Density)
1 = Fixed (Entered at register No. 3057)
2 = Referred.
Default Value : 0