beautypg.com

3 connection to the mfc010, Connection to the mfc010 – KROHNE MFC 010 C Converter User Manual

Page 10

background image


8

MFC010 Interface Manual

3.3

Connection to the MFC010

1. Unscrew the fixing screw on the junction box cover.

2. Release the two fixing screws holding the cable grip in place and remove the grip.

3. Strip approx. 50mm/2” of the outer casing of the signal cable.

4. Split the screen away from the cores and fold it back on the outer cable.

5. Fit the cable grip and secure, making sure that the screen is gripped under the grip.

6. Connect the four cores to the terminals marked A,B, 12V, - as shown


NOTE: The spring loaded connections are released by depressing the white lever above each
connection

1 Cable Gland

2 Cable Grip/Earth

3 Terminal connections

4 Jumper for EOL resistor (not supplied) – off in position as shown, on in other position

Terminal

Input Connection

12V

V+

-

V-

A

A (RS485-)

B

B (RS485+)