KROHNE MFC 010 C Converter User Manual
Page 14
12
MFC010 Interface Manual
NB
For H azardous A rea appl ications t he us er s hould r efer t o s ection 4.3, on page 17, f or c onnection
details.
NB
For multidrop systems, ensure cycle times are properly calculated to ensure bus speeds are adequate
for the application.
3.5
Installation Guidelines for Electromagnetic Compatibility
Whilst t he M FC010 and i ts as sociated s ensor has been des igned, t ested and c ertified t o m eet the
requirements on international s tandards of E lectromagnetic C ompatibility ( EMC), i t i s t he us ers
responsibility to ensure that the connection guidelines described in this document are followed. In addition
the user should use recognised good practise in the location and cable routing of the MFC010 in relation
to its surrounding environment. The user should consider the following suggestions when installing an
MFC010 into a system.
1. Every effort should be made to avoid significant lengths (>50mm) of unshielded signal wire
when connecting to the system, any terminal connections should be housed in a suitably
shielded enclosure.
2. Avoid routing the cable in groups with or alongside other power carrying cables.
3. Avoid locating the MFC010 or routing the connection cable in close proximity to large
electrically powered equipment, such as pumps, inverters etc.
4. If necessary, route the connection cable through a suitably earthed metal conduit.