background image


34

MFC010 Interface Manual

Register

Description

Discrete Output (Binary) States (and Commands)

0XXXX Registers, Accessed Using Commands 01 and 05

1001

Save Changes to EEPROM

1002

Begin Zero Calibration

1003

Reset Totalisers

CT

1004

Reset Additional Totaliser

1005

Request STANDBY Mode

CT

1006

Request STOP Mode

CT

1007

Request MEASURE Mode

1008

Reset Errors

1009

Reset Warnings

1010

Discard Previous Write Operations

1011

Initiate Single Point Density Calibration

CT

1012

Initiate Two Point Density Calibration

CT

1013

Continue Two Point Density Calibration

CT

1014

Reset to Factory Density Calibration

CT

1015

Save Changes to EEPROM with Mass Total

1016

Save Changes to EEPROM with Volume Total

Discrete Input (Binary) States

1XXXX Registers, Accessed Using Command 02

1001

Supervisor Lock Password State

1002

Service Lock Password State

1003

Custody Transfer Lock Password State

1004

Parameters Changed, Awaiting “Save Changes to EEPROM

1005

System Error Flag

1006

Process Warning Flag

1007

Density Calibration Status

1008

Mass Flow Zero Calibration Status

1009

Process Control Status

Input Registers

3XXXX Registers, Accessed Using Command 04

Single Registers (16 bit Integer Values)

1001

Sensor A Level

1002

Sensor B Level

1003

Drive Level

1004

System State

1005

DCF1

1006

DCF5

Floating Point Values (Accessed in pairs of registers)

3001

Mass Flow

3003

Density