Type, Silenceable, Walktest – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual
Page 83: Type silenceable
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
83
Master Programming Level
Programming
Type
To select the type of control module being programmed, press the 2 key while viewing the Edit
Control Screen #2. This will cause the control panel to display the following Control Type Screens.
Press the down arrow key to view additional screens and selections.
While viewing one of the Control Type screens, select the type of control module being
programmed by pressing the corresponding keypad number key. The display will return to the Edit
Control Screen #2 and indicate the new type selection.
The following table contains control module type codes and their functions which are displayed in
the Control Type screens:
Silenceable
The Silenceable selection allows the programmer to select whether output devices connected to the
control module can be silenced, either by pressing the Alarm Silence key or by enabling
Autosilence. Pressing the 3 key while viewing Edit Control Screen #2 will enable the Silenceable
feature causing the display to read Silenceable Yes. Repeated presses of the 3 key will cause the
display to toggle between Silenceable Yes and Silenceable No.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable devices, which are connected to
a control module, for the Walktest feature, press 1 while viewing the Edit Control Screen #3 until
the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between
Walktest Yes and Walktest No. Refer to “Walktest” on page 144 for additional information.
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
CONTROL TYPE
1=BLANK
2=BELL-CIRCUIT
3=HORN-CIRCUIT
Control Type Screen #1
NOTE: A control relay module set to the Resettable Power type will follow the main circuit board
24 VDC resettable power unless the control relay module is disabled.
Control Type
Special Function
Bell Circuit
NAC Type - supervised
Horn Circuit
NAC Type - supervised
Sounders
NAC Type - supervised
Relay
Ignore Open Circuit
Strobe Circuit
NAC Type - supervised
Control
NAC Type - supervised
Resettable Power
1
1 When using a control relay module to supply resettable
power to conventional 2-wire smoke detectors, the
addressable monitor module must be programmed for
Smoke-Conventional operation
Relay Type - Ignore Open Circuit
HVAC SHUTDN
2
2 For HVAC SHUTDN description, refer to “Control
Module Operation” on page 180.
Relay Type - Ignore Open Circuit
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL
1=WALKTEST
2=ZONE ASSIGNMENT
00 QQ QQ QQ QQ
Edit Control Screen #3