Ann-s/pg serial/parallel interface module, Figure 2.22 ann-s/pg connection to facp – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual
Page 49
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
49
Optional Module Installation
Installation
The following table shows the ANN-80 connections to the MS-9200UDLS.
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must be added to the system via FACP programming. Refer to the programming section titled
“ANN-BUS Options” on page 107 in this manual for detailed programming information. Select
the LCD option for programming.
Trouble Response
If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN-80 will indicate
a trouble condition by NOT turning on its AC Power indicator. The LCD will also display Key Bus
Trouble and the piezo will sound approximately once every 10 seconds. Note that the FACP will
provide no indication of an ANN-80 trouble.
To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address correspond-
ing to the address set on the ANN-80 at the FACP.
ANN-S/PG Serial/Parallel Interface Module
Installation
1.
Ensure that all power (AC and DC) has been removed from the FACP.
2.
Connect the ANN-S/PG to the FACP as illustrated in Figure 2.22
3.
Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address)
to the module
4.
Select the address and configuration options for the ANN-S/PG module as described in the
Programming section of this manual (refer to “ANN-BUS Options” on page 107)
Note that the Auto-configure feature allows the programmer to quickly bring all installed
ANN-BUS modules online (refer to “Auto-Configure” on page 116)
MS-9200UDLS
ANN-80 (TB1)
Terminal GND (-) on TB1
Terminal 1 (-)
Terminal PWR (+)TB1
Terminal 2 (+)
Terminal Data (A) on TB9
Terminal 3 (A)
Terminal Data (B) on TB9
Terminal 4 (B)
(-)
(+)
A
B
B+ A+ B- A- A B
ANN
ACS
SHIELD
SLC
SLC
SLC
SLC
TB9
TB10
A B
+ -
+ 24V -
NON-RST
POWER
+ 24V -
RST
POWER
TB1
JP7
1
2
3
+ -
REMOTE PWR
SUPPLY SYNC
+ -
TB2
Figure 2.22 ANN-S/PG Connection to FACP
ANN-S/PG Module
Cable Connectors for
connection to printer
Parallel
Serial
ANN-BUS and power wiring are
supervised and power-limited
24 VDC
nonresettable