Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual
Page 173
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
173
NFPA Standard-Specific Requirements
NFPA 72 Proprietary Protective Signaling Systems
Figure C.3 Proprietary Protective Signaling System
Form-C relay contact programmed
to activate on Supervisory condition.
Form-C Trouble contact which will
automatically activate on any Trouble condition.
Form-C Alarm contact programmed
to activate on General Alarm.
MS-9200UDLS Main Board
MS-9200UDLS Addressable Fire Control Panel
Notes:
1. Connection between the MS-9200UDLS and the
transmitter are supervised by the transmitter.
2. This MS-9200UDLS/Transmitter arrangement can be
employed for NFPA 72 Proprietary Protective Signaling
System.
3. Potter Electric Model EFT-C has not been tested for UL
864 9th Edition and is for use in retrofit applicationsonly.