Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual
Page 43
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
43
Optional Module Installation
Installation
The following formulas were used to generate the wire distance chart:
Exception: When using the ANN-RLY module, the installer must ensure that the maximum
24VDC power line drop does not exceed 0.3 volts. This results in the following wiring limitations:
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
•
3 ANN-80 Remote Fire Annunciators
•
1 ANN-S/PG Serial/Parallel Printer Interface Module
The total worst case current is calculated as follows:
Using this value and referring to the Wiring Distance Table 2.1 on page 42, it can be found that the
available options are:
926 feet maximum using 22 Gauge wire
2,344 feet maximum using 18 Gauge wire
3,731 feet maximum using 16 Gauge wire
5,906 feet maximum using 14 Gauge wire
Maximum Resistance (Ohms)
=
6.0 Volts
Total Worst Case Current Draw (amps)
Maximum Wire Length (feet)
=
Maximum Resistance (Ohms)
*500
(6,000 feet maximum)
Rpu
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
Wire Gauge
Ohms per 1,000 feet (Rpu)
22
16.2
18
6.4
16
4.02
14
2.54
Wire Gauge
Maximum Wire Length
18
312 feet
16
497 feet
14
787 feet
12
1,250 feet
ANN-80 Current Draw
= 3 X 0.040 amps
= 0.120 amps
ANN-S/PG Current Draw
= 1 X.0.040 amps
= 0.040 amps
Total Worst Case Current Draw
= 0.160 amps