Fire – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual
Page 171
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
171
NFPA Standard-Specific Requirements
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1.
3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2.
Cut JP3 on the MS-9200UDLS main circuit board to supervise placement of 4XTMF module
and circuit.
3.
Cut JP2 on the MS-9200UDLS main circuit board to enable FACP Supervisory relay.
4.
Refer to “4XTMF Transmitter Module Installation” on page 39 for detailed information.
FIRE
Gamewell Model M34-56 Local
Energy Municipal Box
Polarities shown in alarm condition
+
Nonpower-limited
Municipal Box
Circuit
+
-
-
4XTMF
Figure C.1 Municipal Box Connected to 4XTMF Transmitter Module