3 controls and indicators, Controls and indicators – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual
Page 17
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
17
Controls and Indicators
Product Description
The following figure illustrates the maximum current that is possible for each major panel output
circuit and the total current available from the FACP.
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle LCD display.
The display includes a long life LED backlight that remains
illuminated. If AC power is lost and the system is not in
alarm, the LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
•
AC Power (green)
•
Fire Alarm (red)
•
Supervisory (yellow)
•
Trouble (yellow)
•
Maintenance (yellow)
•
Alarm Silenced signals (yellow)
•
Disabled (yellow)
•
Battery fault (yellow)
•
Ground fault (yellow)
Figure 1.1 Current Availability
p
o
wer
d
ist9
20
0u
d
2
.wmf
Refer to the battery calculations section for additional information.
6.0 amps with optional
second XRM-24B(E)
transformer.
3.0 amps max. with only
standard transformer
installed.
Standby
2.0 amps
max
per panel
Special Application
Nonresettable or
Resettable Power
Special Application
Resettable or
Nonresettable Power
NAC #1
NAC #3
NAC #2
NAC #4
1.0 amp max
per circuit
1.0 amp max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
Alarm
6.0 amps
max
per panel
0.35 amp max
per circuit
Remote
Synchronization
Output
HONEYWELL
LIFE SAFETY
SYSTEM ALL NORMAL
10:00A 012102