Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual
Page 78
78
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Programming
Master Programming Level
Monitor module type selection will affect the function of the point as follows:
Monitor Type
Action When Activated
Pull-Station
Fire Alarm
User-Defined-1
same as previous (Pull-Station)
Waterflow
Fire Alarm Delayed
User-Defined-2
same as previous (Waterflow)
Monitor
Fire Alarm
User-Defined-3
same as previous (Monitor)
Future
not used
Future
not used
Smoke-Conventional
Fire Alarm
User-Defined-5
same as previous (Smoke-Conventional)
Heat-Conventional
Fire Alarm
User-Defined-6
same as previous (Heat-Detector)
Medic-Alert
1
1 Combination systems employing these non-fire monitor types require the SLC
loop to be programmed by the installer for Style 4 operation and isolator modules
must be employed on each non-fire branch of the SLC as per Figure 13 in the
SLC Wiring Manual (document number 51309). Fire and non-fire devices must
not be used on the same SLC branch. For UL2017 compliance, The ANN-LED
annunciator must be used to indicate the active, dedicated zone or device
General Purpose Signaling, latching
User-Defined-7
same as previous (Medic-Alert)
Hazard-Alert
General Purpose Signaling, latching
User-Defined-8
same as previous (Hazard-Alert)
Tornado-Alert
General Purpose Signaling, latching
User-Defined-9
same as previous (Tornado-Alert)
Phone
Active Phone (LCD display only)
User-Defined-10
same as previous (Phone)
Tamper
Supervisory, nonlatching (tracking)
User-Defined-11
same as previous (Tamper)
Supervisory
Supervisory, latching
User-Defined-12
same as previous (Supervisory)
Supervisory-AR
2
2 For entries ending in AR, AR refers to AutoResettable.
Supervisory, nonlatching (tracking)
User-Defined-13
same as previous (Supervisory-AR)
HVAC OVRRIDE
3
3 For HVAC RESTART and HVAC OVRRIDE descriptions, refer to “Monitor
Module Operation” on page 180.
Switch Supervisory, nonlatching (tracking)
Power-Monitor
Power Fault
User-Defined-14
same as previous (Power Monitor)
Trouble-Monitor
Trouble
User-Defined-15
same as previous (Trouble Monitor)
Process-Monitor
General Purpose Signaling, latching
User-Defined 16
same as previous (Process-Monitor)
Process-Monitor-AR
General Purpose Signaling, nonlatching (tracking)
User-Defined-17
same as previous (Process-Monitor-AR)
MNS Event
Allows the Mass Notification System to override FACP programming and
turn off designated active outputs
Future
not used
Ack-Switch
Acts like panel Acknowledge Key
Sil-Switch
Acts like panel Silence Key
Reset-Switch
Acts like panel Reset Key
Drill-Switch
Acts like panel Drill Key
PAS-Bypass
PAS Disable
HVAC RESTART
Switch (see note 2)
Drill-Switch-AR
Acts like panel Drill Key, nonlatching (tracking)
Table 3.1 Monitor Types