Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual
Page 119
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
119
Master Programming Level
Programming
To select the type, press 1 while viewing the Secondary Phone Line screen. The following screen
will be displayed:
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33, or 3
to select Rotary dialing with a make/break ratio of 62/38.
Service Terminal
The FACP can be programmed remotely from a PC using a modem and telephone line.
Information can also be retrieved from the FACP using the same method. The Upload/Download
option allows an operator to set the necessary parameters to allow the uploading and downloading
of data between the FACP and PC. The Service Terminal selection provides the means for entering
these parameters.
Pressing 1 while viewing On Board DACT Screen #2 will cause the following screen to appear:
Ring Count
The ring count designates the number of rings allowed on the phone line prior to answering an
incoming call from a service terminal. The factory default is 0 which means the control panel will
not answer an incoming call. This entry may be programmed for 1 to 25 rings.
To change the Ring Count, press 1 while viewing the Service Terminal Screen #2. The following
screen will be displayed:
A flashing cursor will appear in the lower left corner of the display. Enter the two-digit ring count
which can be a value between 00 and 25. After the second digit is entered, the display will return to
the Service Terminal screen.
Central Station
Central Station programming configures the control panel DACT for contacting the central station.
Pressing 2 while viewing On Board DACT Screen #2 will cause the following screens to be
displayed:
Reporting Enable
To enable the DACT for reporting FACP activity to the central station, press 1 while viewing
Central Station Screen #1 so the display reads Reporting Enabled. Each press of the 1 key will
toggle the display between Reporting Disabled and Reporting Enabled.
PHONE LINE
1=TOUCHTONE
2=ROTARY 67/33
3=ROTARY 62/38
Secondary Phone Type Screen
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
SERVICE TERMINAL
1=RING COUNT 00
Service Terminal Screen
SERVICE TERMINAL
1=RING COUNT
Service Terminal Screen
RING COUNT
RANGE 0-25 RANGE
Ring Count Screen
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
CENTRAL STATION
1=REPORTING DISABLD
2=REPORT BACKUP
3=CALL LIMIT
Central Station Screen #1
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2