Section 3: programming, 1 programming data entry, Programming data entry – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual
Page 63
63
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Section 3: Programming
3.1 Programming Data Entry
Programming can be accomplished using the MS-9200UDLS keypad or by connecting an optional
standard computer keyboard. The keyboard can be connected to the PS-2 connector J3 on the
control panel main circuit board.
The information presented in this section refers to programming the MS-9200UDLS via the
onboard keypad. If an optional computer keyboard is connected to the MS-9200UDLS main circuit
board, the following table describes the keyboard keys which correspond to the onboard keypad
keys.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for
Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific
values or not used at all as indicated below:
Program feature or
option
Permitted in
UL 864? (Y/N)
Possible settings
Settings permitted in UL
864
Trouble Call Limit
N
Refer to “Trouble Call Limit (Dialer Runaway Prevention)” on
page 120.
Trouble Call Limit = 0 (factory default): unlimited calling to
Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique trouble
to from 1 to 99 within a 24 hour period
Trouble Call Limit = 0 for
unlimited Central Station
trouble calls
Remote Download
Y
Refer to “Remote Site Upload/Download” on page 156.
Remote Download - Proprietary No
Remote Download - Proprietary Yes
Remote Download
Proprietary Yes for
Proprietary system intended
to protect only contiguous
properties
Keypad Keys
Computer Keyboard Keys
1st Event
Home
CLR
Delete
ESC
Esc
RECALL
Insert
*
*
#
#
A - Z
A - Z
0 - 9
0 - 9
■
(on QZ key)
Space bar
—
—
/
/
•
•
ENTER
Enter
ACK/STEP
F1
SILENCE
F2
DRILL
F3
RESET
F4