Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual
Page 48
48
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Installation
Optional Module Installation
Wiring ANN-80 to FACP
The following steps can be used as a guide to wire the annunciator. Make certain all power has
been removed from the FACP prior to annunciator installation.
1.
Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal
block TB1
2.
Remove appropriate amount of wire insulation
3.
Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B).
Make certain to connect A to A and B to B
4.
If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1 terminals
3 & 4. Make certain to connect A to A and B to B
5.
Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2 (+).
Make certain to observe proper polarity
6.
If appropriate, connect the power wiring going to the next device to terminals
1 (-) & 2 (+). Make certain to observe proper polarity
7.
After all connections are made, remove extra wire from inside of annunciator by dressing it
neatly through wire channel, with any excess wire pushed back through hole into electrical box
wiring channel
wires
TB1
a
n
n
-8
0
b
o
x
in
s
id
e
.w
m
f
B+ A+ B- A- A B
ANN
ACS
SHIELD
SLC
SLC
SLC
SLC
TB9
TB10
TB1
B A (+) (-)
4 3 2 1
A B
+ -
+ 24V -
NON-RST
POWER
+ 24V -
RST
POWER
TB1
JP7
1
2
3
+ -
REMOTE PWR
SUPPLY SYNC
+ -
TB2
Figure 2.21 ANN-80 Wiring to FACP
ANN-80
ANN-BUS and power wiring are
supervised and power-limited
24 VDC
nonresettable
ANN-BUS
9
2
u
d
ls
c
to
a
n
n
8
0
.w
m
f
Primary ANN-BUS
MS-9200UDLS