MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Programming
Master Programming Level
Annunciator addressing is specific to the MS-9200UDLS control panel. The following table
describes the annunciator addresses and the corresponding addressable devices that will be annun-
ciated at each annunciator address.
The MS-9200UDLS must be programmed for the annunciators installed on the system. Refer to
“Annunciators” on page 105 for information on annunciator programming. Make certain to
program the annunciator addresses that have been physically installed on the system.
ACS Annunciator Address
Annunciator Displays the Following Points
1
8 General System Status Points & Zones 1 - 56
2
Zones 57 - 99 & 4 NACs
3
SLC Loop, Module Addresses 1 - 64
4
not used
5
SLC Loop, Module Addresses 65 - 99
6
not used
7
not used
8
SLC Loop, Detector Addresses 1 - 64
9
not used
10
SLC Loop, Detector Addresses 65 - 99
11
not used
12
not used
13
not used
14
not used
15
not used
16
not used
17
not used
18
not used
19
not used
20
8 General System Status Points & Zones 1 - 56
21
Zones 57 - 99 & 4 NACs
22
SLC Loop, Module Addresses 1 - 64
23
not used
24
SLC Loop, Module Addresses 65 - 99
25
not used
26
not used
27
SLC Loop, Detector Addresses 1 - 64
28
not used
29
SLC Loop, Detector Addresses 65 - 99
30
not used
31
not used
32
not used
NOTE: The 8 General System Status Points include the following:
• General Alarm
• General Trouble
• General Supervisory
• Alarm Silenced
• System Off Normal
• AC Loss
• Battery Fault
• NAC Fault