Installation
Optional Module Installation
Before installing the module, place the disconnect switch to the right (disconnect) position to pre-
vent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after
the module is installed in the MS-9200UDLS. In addition, the System Trouble LED will turn on to
indicate the Disconnect condition.
The following steps must be followed when installing the 4XTMF module:
1.
Remove all power (Primary and Secondary) from the FACP before installing 4XTMF.
2.
Cut jumper JP3 on the main circuit board to allow the control panel to supervise the 4XTMF
module.
3.
Carefully plug the connectors on the 4XTMF module into connectors J5 and J6 on the MS-
9200UDLS main circuit board, being careful not to bend any pins.
4.
Secure 4XTMF module to standoffs with supplied screws.
5.
Reapply power to the FACP.
6.
For proper 4XTMF operation, the output relays must be programmed for the factory default
settings: Alarm Relay 1, Trouble Relay 2 and Supervisory Relay 3.
7.
When the installation has been complete, enable the 4XTMF module by sliding the disconnect
switch to the left.
8.
Test system for proper operation.
Figure 2.16 4XTMF Transmitter Module
Connect to FACP J5 & J6
Disconnect Switch
shown in
disconnect position
TBL Jumper
Remote Alarm (power-limited)*
Remote Trouble (power-limited)*
No connection
Municipal Box (nonpower-limited)*
1 2 3 4 5 6 7
+ - + - + -
Polarities are shown for module activation
Note: The 4XTMF Module is not directly suitable for transmitting a reverse polarity
supervisory signal. For applications using reverse polarity of a supervisory signal, refer to
“FACP with Keltron” on page 176.
* Wiring from these
terminals can exit the
protected premises.
Dummy load
terminals 6 and 7
(4.7k
, ¼ watt
resistor) if Municipal
Box is not connected.
Disconnect LED
4
x
tm
f.
w
m
f