1 system point, System point – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual
Page 145
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
145
Read Status
Operating Instructions
The following screens will be displayed:
4.23.1 System Point
Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed:
The operator selects the type of device which is to be viewed by pressing 1 for Detector or 2 for
Module. If 1 is pressed, the display will change to the following screen:
Entering the three digit detector address will cause the control panel to display the current status of
the selected device. For example, if a detector with address 001 on the SLC loop is entered, a
display similar to the following will appear:
The information in the preceding display includes:
•
NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)
•
SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be
ION for ionization smoke detector)
•
NORTH CLASSROOM - the Adjective/Noun label for this device
•
Z005 - the first of five possible assigned software zones
•
1D001 - 1 = SLC Loop, D = Detector, 001 = Address 001
•
V - Alarm Verification Enabled (V = Yes, * = No)
•
S - Silenceable for control modules (S = Yes, * = No)
•
W - Walktestable for control and monitor modules (W = Yes, * = No)
Pressing the down arrow key, while viewing the screen shown above, will allow the operator to
view additional programming information about the selected device, such as:
•
Enable/Disable Status
•
Device Type
•
Alarm Verification On/Off (for detectors)
•
Walktest Yes/No
•
PAS (Positive Alarm Sequence) Yes/No (for detectors only)
READ STATUS
1=SYSTEM POINT
2=ZONES
3=POWER
READ STATUS
1=TROUBLE REMINDER
2=TIMERS
3=NACS
Read Status Screen #1
Read Status Screen #3
READ STATUS
1=RELAYS
2=PROGRAM CHECK
3=HISTORY
Read Status Screen #5
READ STATUS
1=ANNUNCIATORS
2=PHONE LINE
3=CENTRAL STATION
Read Status Screen #2
READ STATUS
1=SERVICE TERMINAL
2=PRINTER/PC
3=PRINT
Read Status Screen #4
READ STATUS
1=TIME-DATE
Read Status Screen #6
READ STATUS
1=SYSTEM POINT
2=ZONES
3=POWER
Read Status Screen #1
READ SYSTEM POINT
SELECT TYPE
1=DETECTOR
2=MODULE
READ SYSTEM POINT
ENTER DETECTOR#
NORMAL SMOKE(PHOTO)
NORTH CLASSROOM
Z005
V 1D001