Appendix I: Canadian Application
•
The MS-9200UDLSC is supplied with the DP-9692 Dress Panel.
•
When installing and programming the FACP, the Canadian Option must be set to ON prior to
any other panel programming (refer to “Canadian Option” on page 100 of the Programming
Section of this manual).
•
ACS Series annunciators are not compatible for Canadian applications.
•
At least one ANN-LED must be installed adjacent to the FACP as it is part of the primary
operator interface. Wiring to the ANN-LED must be in metal conduit and must be connected
to the FACP’s Primary ANN-BUS.
•
If remote indicators are desired, they must be connected to the Secondary ANN-BUS circuit
and the other special application power output.
•
The installer must write in the Date of Final Assembly on the Master Marking and Warranty
Label located on the FACP backbox door.
•
To comply with CAN/ULC-S559-04, the 4XTMF option must be utilized along with the
configuration shown in Figure I.3.
•
Positive Alarm Sequence (PAS), the Pre-Signal option, and the Silence Inhibit Timer are not
available for Canadian applications.
FIRE SYSTEM
ACTIVE
SYSTEM
CONTROL
ALL
CALL
1
2
3
4
5
6
7
8
9
10
11
12
13
18
19
20
21
22
23
24
16
17
14
15
LIT
FI
®
AL
by Honeywell
Figure I.1 FACP Minimum Configuration - Single ANN-LED
FACP
ANN-LED
ANN-LED
ANN-80C
ANN-I/O
ANN-S/PG
ANN-RLY
Optional Secondary ANN-BUS (data on
connector TB8, power on TB1 Terminals
3&4 with JP6 pins 1&2 jumpered)
Primary ANN-BUS
(data on connector
TB9, power on TB1
Terminals 1&2)
in metal conduit
(adjacent to FACP)
9
2
0
0
u
ls
c
-a
n
n
le
d
.w
m
f
optional
ECC-50/100
audio system