MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Programming
Master Programming Level
Report Style
Pressing 3 while viewing Central Station Screen #2 will cause the Report Style display to toggle
between Point and Zone. Setting the Report Style to Point will program the DACT to report
individual point status to the Central Station. The control panel is capable of monitoring a total of
198 addressable devices. Setting the Report Style to Zone will program the DACT to report zone
status to the Central Station. The control panel is capable of monitoring a total of 99 individual
zones.
Supervised Phone Line
The Supervised Phone Line feature allows the user to disable the supervision of Phone Line 2 by
the DACT when using an alternate means of secondary transmission path. The factory default
setting is Phone Line 2 supervised.
Pressing 2 for Superv Phone Line while viewing Onboard DACT Screen 2 will cause the following
screen to be displayed:
Each press of the 1 key while viewing this screen will toggle the option between Supervise Phone
Line 2 Yes and No.
ACS/ANN-BUS FAULT
333
000
000
EM
EN
LCD_80F FAULT
330
000
000
EM
EN
NAC 1 DISABLE
521
001
001
ET
ER
NAC 2 DISABLE
522
002
002
ET
ER
NAC 3 DISABLE
526
003
003
ET
ER
NAC 4 DISABLE
527
004
004
ET
ER
CS CALC FAULT
304
000
000
YF
CHARGER FAULT
300
000
000
YP
YQ
OPTION CARD 1 FAULT
331
000
000
ET
ER
REMOTE SYNC FAULT
332
000
000
OU
OV
ZONE DISABLE
570
000
000
FB
FU
NAC_KEY_FLT
300
000
000
ET
ER
NO_DEVICES_INSTLLD
380
000
000
ET
ER
OFF_NORMAL_MESSAGE
308
000
000
LB
LX
24_HOUR_TEST
602
000
000
RP
24 HOUR ABNORMAL TES
608
000
000
RY
UPDOWN REQUEST
411
000
000
RB
UPLOAD SUCCESS
416
000
000
RS
DOWNLOAD SUCCESS
412
000
000
RS
UPDOWN FAILURE
413
000
000
RR
GENERAL_ALARM
000
000
000
00
00
GENERAL_SUPERVISORY
000
000
000
00
00
MNS OVERRIDE
580
000
000
00
00
AUDIO MESSAGE
000
000
Message #
00
00
Table 3.11 Event Codes (Continued)
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE POINT
Central Station Screen #2
NOTES:
1. Detector Address 01 will be reported to the Central Station as Point 01, Detector Address 02
as Point 02, with reports continuing in a similar fashion all the way up to Detector Address 99
which will be reported as Point 99.
2. Module Address 01 will be reported to the Central Station as Point 160, Module Address 02 will
be reported to the Central Station as Point 161, with reports continuing in a similar fashion all the
way up to Module Address 99 which will be reported as Point 258.
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
SUPERVISE PHONE LINE
1=PHONE LINE 2 YES
Supervised Phone Line Screen