Ann-lc lite-connect module – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual
Page 58
58
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Installation
Optional Module Installation
ANN-RLY Board Layout and Connection to FACP
Figure 2.30 illustrates the ANN-RLY board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-LC Lite-Connect Module
Specifications
•
Operating Voltage: 24 VDC
•
Max. Current: 150 mA
•
Operating Temperature: 32°F to 120°F (0°C to 49°C)
•
For indoor use in a dry location only
Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the commu-
nication module.
TB1
J1
SW1
JP
2
ANN-BUS
1 2 3 4 5 6 7 8
TB6
TB3
TB5
TB4
TB2
B+ A+ B- A- A B
ANN
ACS
SHIELD
SLC
SLC
SLC
SLC
TB9
TB10
A B
+ -
+ 24V -
NON-RST
POWER
+ 24V -
RST
POWER
TB1
JP7
1
2
3
+ -
REMOTE PWR
SUPPLY SYNC
+ -
TB2
Figure 2.30 ANN-RLY Board Layout and Connection to FACP
ANN-RLY
Primary ANN-BUS
+24 VDC
-24 VDC
ANN-BUS and power wiring are
supervised and power-limited
9
2
u
d
ls
c
to
rl
y
.w
m
f
MS-9200UDLS
ANN-BUS (ID#)
Address DIP switch