80
2080 BACKUP_
RETURN_
SENSOR1
0 (DISABLE)
O/S
Setting 1 in this parameter switches the value
to be output from the sensor 2 input back to
the sensor 1 input:
0 = DISABLE
1 = ENABLE
81
2081 SENSOR_
BURNOUT_
DETECT
0 (on)
O/S
Switches on and off the sensor burnout
detection:
0 = On
1 = Off
In most cases, this parameter should be set to
0(ON). If this is set to OFF, the sensor burnout
detecting function will not correctly work.
82
2082 LIMSW_1_VALUE_
D
—
—
Indicates the value and status of limit switch 1.
83
2083 LIMSW_1_TARGET 0
O/S
Value to be monitored by limit switch 1:
0 = PRIMARY_VALUE_1
1 = PRIMARY_VALUE_2
2 = SECONDARY_VALUE
3 = DIFFERENTIAL_VALUE
4 = AVERAGE_VALUE
5 = BACKUP_VALUE
84
2084 LIMSW_1
_SETPOINT
0
O/S
Threshold of switching on limit switch 1
85
2085 LIMSW_1_ACT
_DIRECTION
0 (high-limit switch) O/S
Type of limit switch 1:
0 = HI LIMIT (high-limit switch)
1 = LO LIMIT (low-limit switch)
86
2086 LIMSW_1
_HYSTERESIS
0
O/S
Hysteresis of limit switch 1. Input of only a
positive number is valid.
87
2087 LIMSW_1_UNIT
—
—
Unit of LIMSW_1_SETPOINT and LIMSW_1_
HYSTERESIS
88
2088 LIMSW_2_VALUE_
D
—
—
Indicates the value and status of limit switch 2.
89
2089 LIMSW_2_TARGET 0
O/S
Value to be monitored by limit switch 2. The
setting and the corresponding value are the
same as those for limit switch 1 (LIMSW_1_
TARGET).
90
2090 LIMSW_2
_SETPOINT
0
O/S
Threshold of switching on limit switch 2
91
2091 LIMSW_2_ACT_
DIRECTION
0 (high-limit switch) O/S
Type of limit switch 2. The setting and the
corresponding type are the same as those for
limit switch 1 (LIMSW_1_ACT_DIRECTION).
92
2092 LIMSW_2
_HYSTERESIS
0
O/S
Hysteresis of limit switch 2. Input of only a
positive number is valid.
93
2093 LIMSW_2_UNIT
—
—
Unit of LIMSW_2_SETPOINT and LIMSW_2_
HYSTERESIS
94
2094 LIMSW_3_VALUE_
D
—
—
Indicates the value and status of limit switch 3.
95
2095 LIMSW_3_TARGET 0
O/S
Value to be monitored by limit switch 3. The
setting and the corresponding value are the
same as those for limit switch 1 (LIMSW_1_
TARGET).
96
2096 LIMSW_3
_SETPOINT
0
O/S
Threshold of switching on limit switch 3
97
2097 LIMSW_3_ACT
_DIRECTION
0 (high-limit switch) O/S
Type of limit switch 3. The setting and the
corresponding type are the same as those for
limit switch 1 (LIMSW_1_ACT_DIRECTION).
98
2098 LIMSW_3
_HYSTERESIS
0
O/S
Hysteresis of limit switch 3. Input of only a
positive number is valid.
99
2099 LIMSW_3_UNIT
—
—
Unit of LIMSW_3_SETPOINT and LIMSW_3_
HYSTERESIS