A1-2 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual
Page 59

A1-2
IM 01C50T02-01E
Relative
Index
Index Parameter Name
Factory Default
Write
Mode
Explanation
16
1016 RESTART
—
—
Allows a manual restart to be initiated. Several
degrees of restart are possible. They are 1: Run,
2: Restart resource, 3: Restart with defaults defined
in FF specification*
1
, and 4: Restart processor.
17
1017 FEATURES
Soft write lock
supported
Report
supported
—
Used to show supported resource block options.
18
1018 FEATURE_SEL
Soft write lock
supported
Report
supported
—
Used to select resource block options.
19
1019 CYCLE_TYPE
Scheduled
—
Identifies the block execution methods available for
this resource.
bit0: Scheduled
bit1: Event driven
bit2: Manufacturer specified
20
1020 CYCLE_SEL
Scheduled
—
Used to select the block execution method for this
resource.
21
1021 MIN_CYCLE_T
3200 (100ms)
—
Time duration of the shortest cycle interval of which
the resource is capable.
22
1022 MEMORY_SIZE
0
—
Available configuration memory in the empty
resource. To be checked before attempting a
download.
23
1023 NV_CYCLE_T
0
—
Interval between writing copies of NV parameters to
non-volatile memory. Zero means never.
24
1024 FREE_SPACE
0
—
Percent of memory available for further
configuration. YTA has zero which means a
preconfigured resource.
25
1025 FREE_TIME
0
—
Percent of the block processing time that is free to
process additional blocks. YTA does not support
this.
26
1026 SHED_RCAS
—
—
Time duration at which to give up on computer
writes to function block RCas locations. YTA does
not support this.
27
1027 SHED_ROUT
—
—
Time duration at which to give up on computer
writes to function block ROut locations. YTA does
not support this.
28
1028 FAULT_STATE
1: Clear
—
Condition set by loss of communication to an
output block, failure promoted to an output block
or a physical contact. When fail-safe condition is
set, Then output function blocks will perform their
FSAFE actions.
29
1029 SET_FSTATE
1: OFF
—
Allows the fail-safe condition to be manually
initiated by selecting Set.
30
1030 CLR_FSTATE
1: OFF
—
Writing a Clear to this parameter will clear the
device fail-safe state if the field condition, if any, has
cleared.
31
1031 MAX_NOTIFY
3
—
Maximum number of unconfirmed notify messages
possible.
32
1032 LIM_NOTIFY
3
Auto
Maximum number of unconfirmed alert notify
messages allowed.
33
1033 CONFIRM_TIME
640000
Auto
The minimum time between retries of alert reports.
34
1034 WRITE_LOCK
1: Not Locked
Auto
If set, no writes from anywhere are allowed, except
to clear WRITE_LOCK. Block inputs will continue to
be updated
35
1035 UPDATE_EVT
—
—
This alert is generated by any change to the static
data.