A1.2 al function block, A1.2, A1-3 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual
Page 60

A1-3
IM 01C50T02-01E
Relative
Index
Index Parameter Name
Factory Default
Write
Mode
Explanation
36
1036 BLOCK_ALM
—
—
The block alarm is used for all configuration,
hardware, connection failure or system problems
in the block. The cause of the alert is entered in the
subcode field. The first alert to become active will
set the Active status in the Status attribute. As soon
as the Unreported status is cleared by the alert
reporting task, another block alert may be reported
without clearing the Active status, if the subcode
has changed.
37
1037 ALARM_SUM
Enable
—
The current alert status, unacknowledged states,
unreported states, and disabled states of the
alarms associated with the function block.
38
1038 ACK_OPTION
0xffff: unack
Auto
39
1039 WRITE_PRI
0
Auto
Priority of the alarm generated by clearing the write
lock.
40
1040 WRITE_ALM
—
—
This alert is generated if the write lock parameter is
cleared.
41
1041 ITK_VER
4
—
Version number of interoperability test by Fieldbus
Foundation applied to YTA.
42
1042 SOFT_REV
—
YTA software revision number.
43
1043 SOFT_DESC
—
Yokogawa internal use.
44
1044 SIM_ENABLE_MSG Null
Auto
Software switch for simulation function.
45
1045 DEVICE_STATUS_1 0
—
Device status (VCR setting etc.)
46
1046 DEVICE_STATUS_2 0
—
Device status (failure or setting error etc.)
47
1047 DEVICE_STATUS_3 0
—
Device status (failure or setting error etc.)
48
1048 DEVICE_STATUS_4 0
—
Device status
49
1049 DEVICE_STATUS_5 0
—
Device status
50
1050 DEVICE_STATUS_6 0
—
Device status
51
1051 DEVICE_STATUS_7 0
—
Device status
52
1052 DEVICE_STATUS_8 0
—
Device status
*1: FF-891 “Foundation
TM
Specification Function Block Application Process Part 2”
A1.2 Al Function Block
Relative
Index
Index
Parameter
Name
Factory
Default
Write
Mode
Explanation
AI1 AI2 AI3 AI4
0
4000 4100 4200 4300 Block Header TAG:“AI1”,
“AI2”,“AI3” or
“AI4”
Block Tag
= O/S
Information on this block such as Block
Tag, DD Revision, Execution Time etc. The
value for “Period of Execution” should be
larger than “Execution Time.”
1
4001 4101 4201 4301 ST_REV
—
—
The revision level of the static data
associated with the function block. The
revision value will be incremented each
time a static parameter value in the block is
changed.
2
4002 4102 4202 4302 TAG_DESC
(blank)
Auto
The user description of the intended
application of the block.
3
4003 4103 4203 4303 STRATEGY
1
Auto
The strategy field can be used to identify
grouping of blocks. This data is not
checked or processed by the block.
4
4004 4104 4204 4304 ALERT_KEY 1
Auto
The identification number of the plant unit.
This information may be used in the host
for sorting alarms, etc.
5
4005 4105 4205 4305 MODE_BLK AI1,AI2:Auto
AI3,AI4:O/S
Auto
The actual, target, permitted, and normal
modes of the block.
6
4006 4106 4206 4306 BLOCK_ERR —
—
This parameter reflects the error status
associated with the hardware or software
components associated with a block. It is
a bit string, so that multiple errors may be
shown.