Yokogawa Wireless Temperature Transmitter YTA510 User Manual
Page 40

<7. Errors and Warnings>
7-9
IM 01C50T02-01E
Table 7.11
Example of Warning Masking Settings
Case
Device Configurations
WARNING_
ENABLE_1
WARNING_
ENABLE_2
WARNING_
ENABLE_3
WARNING_
ENABLE_4
1
Sensor 2 is not used. Only AI1 is used.
0x7800 0000
0x0000 0000
0x6000 0000
0x2000 0000
2
Sensors 1 and 2 are used.
AI1 and AI2 are used.
0x7f00 0000
0x0000 0000
0x6060 0000
0x3000 0000
3
Sensors 1 and 2 are used.
AI1 and DI1 are used.
0x7800 7000
0x0000 0000
0x6060 0000
0x2000 0000
Table 7.12
Types of Warnings Displayed in Each of Cases 1 to 3
Parameter
Warning
Bit
Case 1
Case 2
Case 3
WARNING_
ENABLE_1
AI1 in O/S mode (AL100)
0x4000 0000
AI1 in MAN mode (AL101)
0x2000 0000
AI1 in Simulate active (AL102)
0x1000 0000
AI1 Non-Scheduled (AL103)
0x0800 0000
AI2 in O/S mode (Al104)
0x0400 0000
AI2 in MAN mode (AL105)
0x0200 0000
AI2 in Simulate active (AL106)
0x0100 0000
AI3 in O/S mode (AL108)
0x0040 0000
AI3 in MAN mode (Al109)
0x0020 0000
AI3 in Simulate active (AL110)
0x0010 0000
AI4 in O/S mode (AL112)
0x0004 0000
AI4 in MAN mode (Al113)
0x0002 0000
AI4 in Simulate active (AL114)
0x0001 0000
DI1 in O/S mode (AL116)
0x0000 4000
DI1 in MAN mode (AL117)
0x0000 2000
DI1 in Simulae active (AL118)
0x0000 1000
DI2 in O/S mode (AL120)
0x0000 0400
DI2 in MAN mode (AL121)
0x0000 0200
DI2 in Simulate active (AL122)
0x0000 0100
DI3 in O/S mode (AL124)
0x0000 0040
DI3 in MAN mode (AL125)
0x0000 0020
DI3 in Simulate active (AL126)
0x0000 0010
DI4 in O/S mode (AL128)
0x0000 0004
DI4 in MAN mode (AL129)
0x0000 0002
DI4 in Simulate active (AL130)
0x0000 0001
WARNING_
ENABLE_2
PID1 in O/S mode (AL132)
0x2000 0000
PID1 in Bypass active (AL140)
0x0020 0000
PID2 in O/S mode (AL142)
0x0008 0000
PID2 in Bypass active (AL150)
0x0000 0800
WARNING_
ENABLE_3
Sensor1 Temp Too High (AL160)
0x4000 0000
Sensor1 Temp Too Low (AL161)
0x2000 0000
Sensor2 Temp Too High (AL170)
0x0040 0000
Sensor2 Temp Too Low (AL171)
0x0020 0000
WARNING_
ENABLE_4
Stop Detection of Sensor Burnout (AL190)
0x4000 0000
Illegal Unit of AI1 (AL191)
0x2000 0000
Illegal Unit of AI2 (AL192)
0x1000 0000
Illegal Unit of AI3 (AL193)
0x0800 0000
Illegal Unit of AI4 (AL194)
0x0400 0000
Default Address Mode (AL198)
0x0040 0000