<7. Errors and Warnings>
7-3
IM 01C50T02-01E
Table 7.2
Warnings
Code
Displayed
on LCD
Indication of DEVICE_
STATUS_#
Cause
Remedy
AL100
AI1 in O/S mode
The actual mode of the AI1 block
is O/S.
See Table 7.3.
AL101
AI1 in MAN mode
The actual mode of the AI1 block
is Man.
Set the target mode of AI1 to Auto.
AL102
AI1 in Simulate Active
SIMULATE of the AI1 block is
Active.
Set SIMULATE of AI1 to Disabled.
AL103
AI1 Non-Scheduled
Execution of AI1 is not scheduled.
Include AI1 in the schedule (by setting
FB_START_ENTRY.#.)
AL104
AI2 in O/S mode
The actual mode of the AI2 block
is O/S.
See Table 7.3.
AL105
AI2 in MAN mode
The actual mode of the AI2 block
is Man.
Set the target mode of AI2 to Auto.
AL106
AI2 in Simulate active
SIMULATE of the AI2 block is
Active.
Set SIMULATE of AI2 to Disabled.
AL108
AI3 in O/S mode
The actual mode of the AI3 block
is O/S.
See Table 7.3.
AL109
AI3 in MAN mode
The actual mode of the AI3 block
is Man.
Set the target mode of AI3 to Auto.
AL110
AI3 in Simulate active
SIMULATE of the AI3 block is
Active.
Set SIMULATE of AI3 to Disabled.
AL112
AI4 in O/S mode
The actual mode of the AI4 block
is O/S.
See Table 7.3.
AL113
AI4 in MAN mode
The actual mode of the AI4 block
is Man.
Set the target mode of AI4 to Auto.
AL114
AI4 in Simulate active
SIMULATE of the AI4 block is
Active.
Set SIMULATE of AI4 to Disabled.
AL116
DI1 in O/S mode
The actual mode of the DI1 block
is O/S.
See Table 7.3.
AL117
DI1 in MAN mode
The actual mode of the DI1 block
is Man.
Set the target mode of DI1 to Auto.
AL118
DI1 in Simulate active
SIMULATE_D of the DI1 block is
Active.
Set SIMULATE_D of DI1 to Disabled.
AL120
DI2 in O/S mode
The actual mode of the DI2 block
is O/S.
See Table 7.3.
AL121
DI2 in MAN mode
The actual mode of the DI2 block
is Man.
Set the target mode of DI2 to Auto.
AL122
DI2 in Simulate active
SIMULATE_D of the DI2 block is
Active.
Set SIMULATE_D of DI2 to Disabled.
AL124
DI3 in O/S mode
The actual mode of the DI3 block
is O/S.
See Table 7.3.
AL125
DI3 in MAN_mode
The actual mode of the DI3 block
is Man.
Set the target mode of DI3 to Auto.
AL126
DI3 in Simulate active
SIMULATE_D of the DI3 block is
Active.
Set SIMULATE_D of DI3 to Disabled.
AL128
DI4 in O/S mode
The actual mode of the DI4 block
is O/S.
See Table 7.3.
AL129
DI4 in MAN mode
The actual mode of the DI4 block
is Man.
Set the target mode of DI4 to Auto.
AL130
DI4 in Simulate active
SIMULATE_D of the DI4 block is
Active.
Set SIMULATE_D of DI4 to Disabled.
AL132
PID1 in O/S
The actual mode of the PID1 block
is O/S.
See Table 7.3.
AL140
PID1 in Bypass active
The bypass action for PID1 is
active.
Reset BYPASS of PID1 to off.
AL142
PID2 in O/S mode
The actual mode of the PID2 block
is O/S.
See Table 7.3.