A1-9 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual
Page 66

A1-9
IM 01C50T02-01E
Relative
Index
Index
Parameter Name
Default
(factory setting)
Write
Description
36
2036 SENSOR_RANGE_
2
Range of sensor
—
Range of sensor 2.
37
2037 SENSOR_SN_2
—
Auto
Serial number of sensor 2.
38
2038 SENSOR_CAL_
METHOD_2
103
Auto
Calibration method for sensor 2:
103 = Factory trim standard calibration
104 = User trim standard calibration
39
2039 SENSOR_CAL_
LOC _2
—
Auto
Shows and is used to record the location
where sensor 2 was calibrated.
40
2040 SENSOR_CAL
_DATE_2
—
Auto
Shows and is used to record the date when
sensor 2 was calibrated.
41
2041 SENSOR_CAL
_WHO_2
—
Auto
Shows and is used to record the person who
calibrated sensor 2.
42
2042 SENSOR _
CONNECTION_2
As specified by the
customer before
shipment
O/S
Number of connection wires of sensor 2.
43
2043 SECONDARY
_VALUE
—
—
Indicates the terminal board temperature.
44
2044 SECONDARY
VALUE_UNIT
°C
Auto
Unit of the terminal board temperature.
45
2045 MODULE_SN
Serial number
—
Serial number
46
2046 ALARM_SUM
Enable
—
Shows the alarm summary for the transducer
block.
47
2047 PRIMARY_VALUE
_FTIME_1
2 second
O/S
Time constant (in seconds) of the first-order
lag filter applied to the sensor 1 input . (0 to
99)
48
2048 CAL_STATE_1
0 (User Cal Off)
O/S
Indicates the validity of user calibration for
sensor 1:
0 =User Cal Off(Invalidate user-set
calibration values)
1 = User Cal On(Validate user-set calibration
values)
2 = Calibration Exec(User calibration mode)
49
2049 CJC_SELECT_1
0 (internal CJC)
O/S
Selects whether the terminal board
temperature or user-set constant
(CONSTANT_CJC_TEMP_1) is to be used
for cold junction compensation (CJC) for the
sensor 1 input. Valid for Thermocouple input
only.
0=Internal CJC
1=Constant CJC
50
2050 CONSTANT_CJC
_TEMP_1
—
O/S
User-set constant for CJC for the sensor 1
input. Setting 0 in this parameter disables
RJC. Valid only when CJC_SELECT_1 is set
to 1.
51
2051 WIRING _
RESISTANCE_1
0
O/S
Wiring resistance of the sensor 1 input. For a
2-wire resistance input, the input resistance
minus this value is used as the temperature
value.
52
2052 SENSOR_MATCH
_R0_1
0
O/S
Value of the factor R0 used in the sensor
matching function for the sensor 1 input
53
2053 SENSOR_MATCH
_A_1
0
O/S
Value of the factor A used in the sensor
matching function for the sensor 1 input
54
2054 SENSOR_MATCH
_B_1
0
O/S
Value of the factor B used in the sensor
matching function for the sensor 1 input
55
2055 SENSOR_MATCH
_C_1
0
O/S
Value of the factor C used in the sensor
matching function for the sensor 1 input
56
2056 SENSOR_MATCH
_ALPHA_1
0
O/S
Value of the factor α used in the sensor
matching function for the sensor 1 input
57
2057 SENSOR_MATCH
_DELTA_1
0
O/S
Value of the factor δ used in the sensor
matching function for the sensor 1 input