3 view object, View object -7 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual
Page 20

<5. Configuration>
5-7
IM 01C50T02-01E
5.6.3 View Object
This is the object to form groups of parameters
in a block. One of advantage brought by forming
groups of parameters is the reduction of load for
data transaction. YTA has four View Objects for
each Resource block, Transducer block and each
function block, and each View Object has the
parameters listed in Table 5.11 to 5.13.
Table 5.10
Purpose of Each View Object
Description
VIEW_1 Set of dynamic parameters required by
operator for plant operation. (PV, SV, OUT,
Mode etc.)
VIEW_2 Set of static parameters which need to be
shown to plant operator at once. (Range
etc.)
VIEW_3 Set of all the dynamic parameters.
VIEW_4 Set of static parameters for configuration or
maintenance.
Table 5.11
View Object for Resource Block
Relative
index
Parameter
VIEW
1
VIEW
2
VIEW
3
VIEW
4
1
ST_REV
2
2
2
2
2
TAG_DESC
3
STRATEGY
2
4
ALERT_KEY
1
5
MODE_BLK
4
4
6
BLOCK_ERR
2
2
7
RS_STATE
1
1
8
TEST_RW
9
DD_RESOURCE
10
MANUFAC_ID
4
11
DEV_TYPE
2
12
DEV_REV
1
13
DD_REV
1
14
GRANT_DENY
2
15
HARD_TYPES
2
16
RESTART
17
FEATURES
2
18
FEATURE_SEL
2
19
CYCLE_TYPE
2
20
CYCLE_SEL
2
21
MIN_CYCLE_T
4
22
MEMORY_SIZE
2
23
NV_CYCLE_T
4
24
FREE_SPACE
4
25
FREE_TIME
4
4
26
SHED_RCAS
4
27
SHED_ROUT
4
28
FAULT_STATE
1
1
29
SET_FSTATE
30
CLR_FSTATE
Relative
index
Parameter
VIEW
1
VIEW
2
VIEW
3
VIEW
4
31
MAX_NOTIFY
1
32
LIM_NOTIFY
1
33
CONFIRM_TIME
4
34
WRITE_LOCK
1
35
UPDATE_EVT
36
BLOCK_ALM
37
ALARM_SUM
8
8
38
ACK_OPTION
2
39
WRITE_PRI
1
40
WRITE_ALM
41
ITK_VER
2
42
SOFT_REV
43
SOFT_DESC
44
SIM_ENABLE_MSG
45
DEVICE_STATUS_1
4
46
DEVICE_STATUS_2
4
47
DEVICE_STATUS_3
4
48
DEVICE_STATUS_4
4
49
DEVICE_STATUS_5
4
50
DEVICE_STATUS_6
4
51
DEVICE_STATUS_7
4
52
DEVICE_STATUS_8
4
Total in byte
22
30
54
31