9. General Specifications
9.1 Standard Specifications
For items other than those described below,
refer to IM 01C50B01-01E.
Applicable Model:
YTA320
Accuracy
See Table 9.1 in Page 9-4.
Ambient Temperature Effect per 10°C Change
See Table 9.2 in Page 9-5.
Output Signal:
Digital communication signal based on
FOUNDATION Fieldbus protocol.
Supply Voltage:
9 to 32 V DC for general use and flameproof
type
9 to 24 V DC for intrinsically safe type Entity
model
9 to 17.5 V DC for intrinsically safe type FISCO
model
Conditions of Communication Line:
Supply Voltage: 9 to 32 V DC
Supply Current: 16.6 mA (max)
Functional Specifications:
Functional specifications for Fieldbus
communication conform to the standard
specifications (H1) of
FOUNDATION Fieldbus.
Function Block:
Four AI function blocks
Four DI function blocks
One/Two PID function blocks (option)
Link Master funtion
< Settings When Shipped >
Sensor type
‘Pt100, 3 wire system’ (for both inputs), or as specified in
order.
Tag Number (PD tag)
‘TT1001’ unless otherwise specified in order. (Not
engraved on tag plate in such case.) *
1
Output Mode (L_TYPE)
‘Indirect’ unless otherwise specified in order
Calibration Range (XD_SCALE) Lower/Higher Range Value ‘0 to 100’, or as specified in order
Unit of Calibration Range
Selected from °C and Kelvin. (Only one unit can be
specified.) When optional code /D2 is specified, °F and °R
can also be specified.
Output Scale (OUT_SCALE) Lower/Higher Range Value
‘0 to 100%’
Damping Time Constant (PV_FTIME of TB)
‘2 sec.’
Node Address (in hexadecimal)
‘0 × F3’ unless otherwise specified in order
BOOT_OPERAT_FUNCTION_CLASS
‘BASIC’ unless otherwise specified in order