d. The following screen will be displayed:

Manually close the breaker. As each contact is closed, the screen will be updated as
shown:

After all of the contacts have been closed, the following screen will be displayed:

Fully close the breaker. When the breaker is at the close position (on latch), press the

[ENTER]

key to find contact wipe.

e. The test results will be printed, and you will be returned to the “START-UP” menu. A

typical “Slow-Close” test results printout is shown in Figure 15.

NOTES

• The “Slow-Close” test report can be saved in the DigiTMR S2’s EEPROM. Please

see section 3.10.1 for information on how to save test records.

• You can calculate contact stroke by adding the contact touch and contact wipe

distances.

LIFT BRKR TO CLS POS
THEN PRESS "ENTER"
TO FIND CONTACT WIPE
LIFT TO CLS BRKR NOW


CONTACT 1: CLOSED
CONTACT 2: CLOSED
CONTACT 3: OPEN

LIFT TO CLS BRKR NOW

CONTACT 1: OPEN
CONTACT 2: OPEN
CONTACT 3: OPEN

LIFT TO CLS BRKR NOW