REV 1 DIGITMR S2 USER’S MANUAL

102

3.12.2. Setting Up the CLOSE Analysis Points

Follow the steps below to setup the CLOSE analysis points:

a. Start from the “START-UP” menu:

Press the

[3]

key (SETUP).

b. The following screen will be displayed:

Press the

[1]

key (ANALYSIS POINTS).

c. The following screen will be displayed:

Press the

[2]

key (CLOSE TIMING).

d. The following screen will be displayed:

Press the

[2]

key (DIST FROM CLOSE).

CLOSE ANALYSIS PT 1

1. PERCENT OF STROKE
2. DIST FROM CLOSE
3. CONTACT #1 CLOSE

1. OPEN TIMING
2. CLOSE TIMING
3. PRINT SETTINGS
4. TEST PLANS


1. ANALYSIS POINTS
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. SHOT DESCRIPTION
5. NEXT PAGE

1. TIME BREAKER
2. GET RESULTS
3. SETUP
4. DIAGNOSTICS