3.7.3. Timing a CLOSE-OPEN Operation Using Contact Channel #1
The CLOSE-OPEN operation of a breaker simulates a condition where a breaker is closed on a
fault. To time a CLOSE-OPEN operation:
a. Start from the “START-UP” menu:
Press the
[1]
key (TIME BREAKER) to start a test.
b. The following screen will be displayed:
Press the
[1]
key (NO).
c. The following screen will be displayed:
Press the
[1]
key (WINDOW = 1 SEC) to select the 1-second timing window.
d. The following screen will be displayed:
Press the
[1]
key (Internal Trigger) to select the internal trigger.
TRIGGER MODE:
1. INTERNAL TRIGGER
2. EXTERNAL TRIGGER
TIMING WINDOW:
1. WINDOW = 1 sec
2. WINDOW = 10 SEC
3. WINDOW = 20 SEC
INSERTION RESISTOR?
1. NO
2. YES
1. TIME BREAKER
2. GET RESULTS
3. SETUP
4. DIAGNOSTICS
- Resistor Transducer Adapter 9095-UC (7 pages)
- Accu-Ohm 200 S2 (4 pages)
- Accu-Trans (28 pages)
- ATO-400 (43 pages)
- ATO-400P (44 pages)
- Auto-Ohm (22 pages)
- Auto-Ohm 100_200 s2 (31 pages)
- Auto‐Ohm 200 S3 (66 pages)
- DMOM-100 (35 pages)
- DMOM-100_200 s2 (42 pages)
- DMOM-200 (33 pages)
- Herculito (17 pages)
- ATRT-01 S2 (59 pages)
- ATRT-01_01B S3 (88 pages)
- ATRT-01_01B_01D (31 pages)
- ATRT-03_03A (114 pages)
- ATRT-03_03A S2 (147 pages)
- CVT-765 (46 pages)
- Tri-Phase (155 pages)
- CBCT (14 pages)
- CBPS-300 (16 pages)
- CT-3500 (24 pages)
- CT-3500 S2 (53 pages)
- CT-6500 (69 pages)
- CT-6500 S2 (82 pages)
- CT-7000 (83 pages)
- CT-7000 S2 (108 pages)
- CT-7000 S3 (137 pages)
- CT-7500 (76 pages)
- CT-7500 S2 (110 pages)
- CT-8000 (120 pages)
- CT-8000 S3 (145 pages)
- DigiTMR (86 pages)
- DigiTMR S2 PC (31 pages)
- MCCB-250 (17 pages)
- UPS S2 (13 pages)
- EZCT-2000 (68 pages)
- EZCT-2000 (45 pages)
- EZCT-2000A (103 pages)
- EZCT-2000B (118 pages)
- EZCT-2000C Plus (119 pages)
- EZCT-S2 (66 pages)
- EZCT-S2A (98 pages)
- IRM-5000P (58 pages)