beautypg.com

30 logic f – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller FLEXIBLE CONTROL STRATEGIES User Manual

Page 49

background image

2.7.30 LOGIC F

The Logic F module executes a selected function on two input variables A and B to produce an out-
put. Input variables A and B, as well as the output, are all logic values (0/1). The table below lists
the input variables; an illustration of the Logic F module follows the table. The function code (FC)
to be executed by the Logic F module is selected from the Logic Functions table at the bottom of
the page and entered into datapoint B211. The function codes are also provided in expanded form
on the next page.

Inputs

WIRELIST

SYMBOL

DATA

TYPE

ASSIGNED VALUE

B209

A

L

B210

B

L

B211

FC

N/A

Output Datapoint: L086

Logic Functions

FC

OUTPUT

FC

OUTPUT

0

A

4

A OR NOT B

1

A OR B

5

A AND NOT B

2

A AND B

6

J-K LATCH

3

A XOR B

7

D LATCH

Invert output if FC = FC + 128

FCS 53MC5000 Flexible Control Strategies

2-42

LOGC-F