14 deviation/alarm calculation 0 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller FLEXIBLE CONTROL STRATEGIES User Manual
Page 28
2.7.14 DEVIATION/ALARM CALCULATION 0
The Deviation/Alarm Calculation 0 (D/C 0) module calculates and loads a Deviation Value (DV),
based upon the Setpoint (SP) and the Process Variable (PV). Before the calculation is performed,
the setpoint value is conditioned not to exceed the T1 rate of change limit. If the calculated devia-
tion falls within the Control Zone (CZ) value, the deviation is forced to 0.0. This module also deter-
mines if alarm conditions exist based on the Control Alarm Mode (AIX), both alarm limits (PL1 and
PL2), and the Alarm Deadband (ADB). Results of the alarm tests are loaded into active alarms 1
and 2 (PA1 and PA2). The tables that follow list the input variables and the parameters (e.g., T1,
AIX, etc.). An illustration of the Deviation/Alarm Calculation 0 module follows the tables.
Inputs
WIRELIST
SYMBOL
DATA
TYPE
ASSIGNED VALUE
B152
PV0
C
B153
SP0
C
Output Datapoints: C119, C121, L110, L111
Parameters
Parameters
SYMBOL
DATAPOINT
ASSIGNED VALUE
SYMBOL
DATAPOINT
ASSIGNED VALUE
T1-0
C117
PL2-0
C104
CZ0
C114
ADB0
C105
PL1-0
C103
AIX0
B335
ADB0...alarm dead band
AIX0...control alarm mode
CZ0...control zone
DV0...deviation
PA1-0...alarm A active
PA2-0...alarm B active
PL1-0...alarm limit 1
PL2-0...alarm limit 2
PV0...process variable
SP0...setpoint
T1-0...setpoint slew rate
TSP0...control setpoint
Section 2. FCS Modules
DAC-0
2-21